EU F-Gas regulations – Manufacturers & Importers of RACHP Equipment

Manufacturers & Importers of RACHP

This guidance is for organisations affected by the 2014 EU F-Gas Regulation (517/2014). The F-Gas
Regulation creates controls on the use and emissions of fluorinated greenhouse gases (F-Gases)
including HFCs, PFCs and SF6.

Manufacturers and importers of refrigeration, air-conditioning and heat pump equipment (RACHP)
using HFC refrigerants have to comply with a number of requirements under the F-Gas Regulation.
The 2014 EU F-Gas Regulation replaces the 2006 Regulation, strengthening all of the 2006
requirements and introducing a number of important new measures.

The F-Gas Regulation is an important piece of legislation that will result in significant reductions in the
emissions of F-Gases. These are very powerful greenhouse gases, with global warming impacts that
are several thousand times higher than CO2 (per kg of gas emitted). All EU Member States agree that
it is important to reduce emissions of these gases.

This Information Sheet describes the requirements that apply to RACHP equipment manufacturers
and importers.

Sector Description

Manufacturers & Importers of RACHP


The RACHP sector covers a wide range of equipment and end users, ranging from small domestic and
commercial systems to large industrial plant.

Key sectors of the RACHP market include:

1. Domestic refrigeration
2. Commercial refrigeration
3. Industrial refrigeration
4. Transport refrigeration
5. Stationary air-conditioning and heat pumps
6. Mobile air-conditioning

 Manufacturers and importers of RACHP equipment that serve these markets must become fully aware of relevant parts of the 2014 F-Gas Regulation so that they can provide suitable equipment to their customers and comply with certain legal obligations.

NEW: Bans on the use of HFCs in certain types of RACHP equipment.

Manufacturers & Importers of RACHP


 

The 2014 Regulation includes a number of HFC bans. Equipment manufacturers and importers must ensure they do not place any banned products on the market.

Manufacturers should also be aware that these bans “do not tell the full story”. The HFC phase down
and the service ban (see below) also have a significant influence on selecting refrigerants for new
plant. Equipment manufacturers may gain a competitive advantage if they can supply equipment that
uses low GWP1 refrigerants.

NEW: Impact of the Service Ban on sales of new equipment

Manufacturers & Importers of RACHP


 

Purchasers of new commercial and industrial refrigeration equipment should be made aware that a
“Service Ban” will affect certain existing systems using HFCs with a GWP above 2,500 from 2020. The
ban applies to systems containing more than 40 tonnes CO2 equivalent (10 kg for HFC 404A). To avoid
future problems manufacturers and importers should advise clients purchasing plants above this size
threshold to select only refrigerants with a GWP below 2,500, with immediate effect. It makes no
sense to be purchasing equipment that will need converting or replacing within just a few years.

NEW: Impact of the HFC Phase Down on the sales of new equipment

Manufacturers & Importers of RACHP


 

When purchasing new RACHP equipment your clients should also consider the HFC phase down7
This will reduce the quantity of HFCs that can be sold in the EU – by 2030 there will be an 80% cut in HFC supply. Equipment bought now will still be operating when deep cuts in HFC supply are in force.
Irrespective of the bans, it will become increasingly important to purchase equipment using refrigerants with the lowest practical GWP to minimise the future impact of the phase down.

HFC Ban in MAC Directive

Manufacturers & Importers of RACHP


 

Mobile air-conditioning (MAC) used in cars and light vans are affected by the MAC Directive
(2006/40/EC). This bans the use of any refrigerant with a GWP above 150 in new car and light van airconditioning systems. The ban applies to new “vehicle types” (i.e. new models) with immediate effect and to all new cars from January 2017. This creates a ban on the standard MAC refrigerant (HFC 134a).

Most car manufacturers are starting to use HFO 1234yf.

Equipment design requirements

Manufacturers & Importers of RACHP


 

It is important to consider the overall aims of the F-Gas Regulation and the obligations that it places
on purchasers of RACHP equipment. Your equipment should be designed to help customers comply
with the F-Gas Regulation. The key design rules are:
a) Use the refrigerant with the lowest practical and cost effective GWP
b) Design the plant for very low leakage
c) For large plant fit an automatic leak detection system

Energy Efficiency is Crucial

Manufacturers & Importers of RACHP


 

When designing RACHP equipment it is also important to maximise the energy efficiency. During the
life cycle of such equipment it is the energy related CO2 emissions that dominate the overall
greenhouse gas emissions. It is counter-productive, from an environmental perspective, to use an
ultra-low GWP alternative but have to sacrifice energy efficiency. Always try to ensure that the low
GWP alternative that you select has equal (or preferably better) energy efficiency to the best high
GWP option available on the market.

Product Labelling

Manufacturers & Importers of RACHP


 

All RACHP products that contain F-Gases (including HFCs) shall not be placed on the market unless the F-Gases are identified with a label.

The label shall indicate the following information:

1) A reference that the RACHP system contains F-Gases
2) The accepted industry designation for the F-Gas concerned or, if no such designation is
available, the chemical name
3) NEW: From 1 January 2017, the quantity expressed in weight and in CO2 equivalent of F-Gas
contained in the equipment, and the global warming potential of the gas
4) If applicable, a reference that the F-Gases are contained in hermetically sealed equipment

NEW: Pre-charged RACHP equipment

Manufacturers & Importers of RACHP


 

From 1st January 2017 RACHP equipment pre-charged with HFCs cannot be placed on the market
unless the HFCs are accounted for within the EU HFC phase down quota system9
This is an important rule that affects all pre-charged RACHP equipment (including both manufactured in the EU and imported).

Examples of equipment affected includes:
a) Hermetically sealed systems (e.g. for commercial refrigeration)
b) Split system and VRV air-conditioning systems
c) Chillers
d) Mono-block heat pumps

For equipment manufactured within the EU, manufacturers should purchase refrigerant from an EU
supplier that holds a quota to sell HFCs under the 2014 F-Gas Regulation. An EU based equipment
manufacturer cannot import HFCs directly from outside the EU unless they hold an import quota.
From January 2017 onwards, any RACHP equipment imported into the EU that is pre-charged with
HFCs, must use HFCs obtained from the EU quota. Importers will need to prove to the authorities that
the equipment they import complies with this requirement.

Non-EU manufacturers will have the option of:

a) Purchasing their required HFCs from an EU quota holder (the quota holder would deliver
actual HFC fluids to the non-EU manufacturer)
b) Obtain an authorisation from an EU quota holder to use a specified amount of their quota (the
non-EU manufacturer will then be able to source the actual HFC fluid from a local supplier)

The compliance information required from manufacturers and importers of pre-charged equipment
includes documentation to show the source of HFCs and a declaration of conformity.
From 1st January 2018, where HFCs contained in the equipment have not been placed on the market
prior to the charging of the equipment, importers of that equipment shall ensure that by 31st March
every year the accuracy of the documentation and declaration of conformity is verified, for the
preceding calendar year, by an independent auditor.

Manufacturers and importers of pre-charged equipment must keep the documentation and
declaration of conformity for a period of at least five years after the placing on the market of that
equipment. Importers of pre-charged equipment must ensure they are registered in the HFC quota
system registry and must submit their verified conformity data to the European Commission annually.

NEW: Reporting Imports of Pre-charged RACHP equipment

Manufacturers & Importers of RACHP


 

Linked to the pre-charge restrictions discussed in the section above is an important new reporting
requirement that applies to importers of pre-charged RACHP equipment. Key requirements include:
• The reporting rules apply to F-Gases being placed on the EU market in all products and
equipment, including RACHP equipment.
• The rules apply to both F-Gases and “gases listed in Annex II”. F-Gases refers to a list in Annex
I of the Regulation and it includes all the currently used HFC refrigerants. The gases in Annex
II includes five of the new HFO11 refrigerants (e.g. HFO 1234yf) and a number of very unusual
gases (not likely to be used in RACHP equipment).
• The reporting threshold is 500 tonnes CO2 per year – this is a low threshold for an equipment
importer. The metric tonne equivalent depends on the GWP of the refrigerant in the imported
equipment12. For HFC 410A, 500 tonnes CO2e is only 0.24 metric tonnes.

• The data that must be reported includes:
a) the categories of the products or equipment containing F-Gases / Annex II refrigerants
b) the number of units placed on the market
c) the quantities of each refrigerant contained in the products or equipment.

• The first report must be made before March 31st 2015 for imports in calendar year 2014.
• It is worth noting that these reporting rules do not apply to pre-charged equipment
manufactured within the EU, as any HFC refrigerants contained in such equipment is already
being reported by the production / import quota holder.

The SRAC industry and the world as a whole, now understand that fluorinated gases have a potentially devastating global warming effect when released into the atmosphere.

F-Gas regulations have been implemented in order to contain, prevent and thereby reduce emissions of fluorinated greenhouse gases.

On 2nd April 2008, the Commission Regulation 303/2008 set out the requirements for a company certification scheme.

This scheme is specifically for businesses working with F-Gas refrigeration, air-conditioning and heat pump equipment containing or designed to contain fluorinated greenhouse gases.

These F-Gas Certification requirements are in accordance with Article 5.1 of EC Regulations 842/2006 on certain fluorinated greenhouse gases (the EC F-Gas Regulation).